DIESEL 1 EN
Motor pump starting control panel for fire-fighting units (UNI EN-12845)
-
Events data logger
Applications
Optional
CARATTERISTICHE GENERALI
- Operating voltage 400Vac ± 10% 50/60Hz
- General disconnecting switch with door lock
- Key selector for automatic/emergency operation
- Emergency start button under breakable glass
- Siren shut-off
- N°2 automatic battery chargers 6A
- Diode bridge 30A
- N°3 relaunch relays
- N°2 power relays to power the starter motor
- Auxiliary circuit protection fuse
- Battery charger protection fuse
- ILME 16-pole socket for connection to the motor (plug supplied)
- Connection terminal board
- External metal box
- Protection degree IP55
- Operating temperature -5/+40°C
VANTAGGI
- Multilingual Display LCD to visualize:
- Battery A voltage
- Battery B voltage
- Motor revs
- Motor temperature
- Fuel level
- Oil pressure
- Oil temperature
- Local temperature
- Water pressure
- Startings counter
- Work hour counter
- Three-phase or single-phase mains supply
- Alarms specifications and delyas adjustable from keyboard
- List of events up to 250 storable
INPUTS/OUTPUTS
- N°2 very low voltage inputs normally closed for start pressure switches
- Input for command from priming tank
- Input for fuel reserve signaling contact
SINGLE-PHASE 230Vac ± 10% 50/60Hz |
|||||||||
CODE | TYPE | STARTING RELAY | POWER SUPPLY | BATTERY | DIMENSIONS mm | WEIGHT | BOX | ||
---|---|---|---|---|---|---|---|---|---|
CURRENT (A) | A-H | L-W | P-D | Kg | |||||
SQ905.00 | DIESEL 1 EN 12 | 800 | 230Vac | 12Vdc | 500 | 400 | 230 | 18 | 50 |
SQ905.01 | DIESEL 1 EN 24 | 800 | 230Vac | 24Vdc | 500 | 400 | 230 | 18 | 50 |