IMPEDANCE PLUS 1
Stator impedance starting electronic control panel 1 motor for the dry running control, clean water and sewage with display
-
Multi application control panel
-
Motor’s data auto learning
-
Well adaptive filling system
-
Events and alarms data logger
-
Protection for motherboard
-
Remote control SALUPO CONNECT
Applications
Optional
GENERAL SPECIFICATIONS
- Operating voltage 400Vac ±10% 50/60Hz
- General disconnecting switch with door lock
- Button for automatic operation
- Button for manual operation (stable/unstable)
- Siren shut-off button
- Adjustable impedance timer
- Auxiliary circuit protection fuse
- Motor protection fuse
- N°2 contactors
- Three-phase impedance with thermostat
- Connection terminal board
- External metal box
- Protection degree IP55
- Operating temperature -5/+40°C
ADVANTAGES
- Multilingual Display LCD to visualize:
- Operating voltage
- Current
- Cosφ
- Hour counter
- Level status
- System pressure with pressure transducer
- Tank level in meters with piezoresistive probe
- All information concerning the operation of the motor
- Motor’s data auto learning:
- Cosφ
- Minimum and maximum current
- Well adaptive filling system
- Adjustable maximum number of startings per hour
- Adjustable motor starting test (24-48-72-96h)
- Dry running with level control, cosφ and minimum current
- Adjustable probe sensitivity
- Emptying (1 input)/Filling (2 inputs) function
- Loss of pressure control
- Adjustable mains supply returning
- Siren shut-off
- Operation with pressure switches, float switches, probes, pressure transducer and piezoresistive probe 4-20mA
INPUTS/OUTPUTS
- N°4 very low voltage inputs
- Input 4-20mA
- Very low voltage input for motor klixon
- N°2 alarm outputs 12Vdc max 200mA for siren and flashing Led lamp
- Alarm output max 5A NC-COM-NO (pure contact)
PROTECTIONS
- Maximum and minimum current protection with alarm
- Lack and sequence of phases protection with automatic resent and alarm
- Minimum and maximum voltage protection with automatic reset and alarm
- Motor klixon protection with automatic reset and alarm
THREE-PHASE 400Vac ± 10% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SQ687.00/I | IMPEDANCE PLUS 1 400 3 | 2,2 | 3 | 4÷9 | 500 | 400 | 230 | 17 | 50 |
SQ687.01/I | IMPEDANCE PLUS 1 400 5,5 | 4 | 5,5 | 8÷12,5 | 500 | 400 | 230 | 17 | 50 |
SQ687.02/I | IMPEDANCE PLUS 1 400 7,5 | 5,5 | 7,5 | 10÷17 | 500 | 400 | 230 | 17 | 50 |
SQ687.03/I | IMPEDANCE PLUS 1 400 10 | 7,5 | 10 | 13÷21 | 500 | 400 | 230 | 20 | 50 |
SQ687.04/I | IMPEDANCE PLUS 1 400 12,5 | 9,2 | 12,5 | 19÷26 | 500 | 400 | 230 | 20 | 50 |
SQ687.05/I | IMPEDANCE PLUS 1 400 15 | 11 | 15 | 22÷30 | 500 | 400 | 230 | 22 | 50 |
SQ687.06/I | IMPEDANCE PLUS 1 400 17,5 | 13 | 17,5 | 25÷33 | 500 | 400 | 230 | 23 | 50 |
SQ687.07/I | IMPEDANCE PLUS 1 400 20 | 15 | 20 | 30÷38 | 600 | 400 | 230 | 24 | 60 |
SQ687.08/I | IMPEDANCE PLUS 1 400 25 | 18,5 | 25 | 38÷50 | 700 | 500 | 240 | 31 | 70 |
SQ687.09/I | IMPEDANCE PLUS 1 400 30 | 22 | 30 | 45÷58 | 700 | 500 | 240 | 33 | 70 |
SQ687.10/I | IMPEDANCE PLUS 1 400 35 | 26 | 35 | 50÷65 | 700 | 500 | 240 | 33 | 70 |
SQ687.11/I | IMPEDANCE PLUS 1 400 40 | 30 | 40 | 60÷75 | 700 | 500 | 240 | 37 | 70 |
SQ687.12/I | IMPEDANCE PLUS 1 400 50 | 37 | 50 | 65÷90 | 800 | 600 | 290 | 48 | 80 |
SQ687.13/I | IMPEDANCE PLUS 1 400 60 | 45 | 60 | 70÷105 | 1000 | 800 | 370 | 82 | 103 |
SQ687.14/I | IMPEDANCE PLUS 1 400 70 | 51,5 | 70 | 75÷110 | 1000 | 800 | 370 | 88 | 103 |
SQ687.15/I | IMPEDANCE PLUS 1 400 75 | 55 | 75 | 75÷110 | 1000 | 800 | 370 | 88 | 103 |
SQ687.16/I | IMPEDANCE PLUS 1 400 80 | 60 | 80 | 80÷150 | 1000 | 800 | 370 | 90 | 103 |
SQ687.17/I | IMPEDANCE PLUS 1 400 90 | 66 | 90 | 80÷150 | 1000 | 800 | 370 | 100 | 103 |
SQ687.18/I | IMPEDANCE PLUS 1 400 100 | 75 | 100 | 90÷180 | 1000 | 800 | 370 | 100 | 103 |
OPTIONALS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
OP100.29/B | On board GPRS expansion | ||||||||
OP100.39/B | On board Ethernet expansion | ||||||||
OP100.49/B | On board MODBUS RS-485 expansion | ||||||||
OP100.59/B | On board Ethernet – WiFi – expansion | ||||||||
OP100.99/B | On board expansion to detect water in the oil chamber up to 3 motors | ||||||||
OP100.01 | 3 level probes kit | ||||||||
OP100.17/024 | Wired 24Vac relay complete with socket | ||||||||
OP100.05/1 | Wired three-phase surge arrester type 2 | ||||||||
SS100.00 | Visual and acoustic alarm indicator (BASIC ALARM VA012) | ||||||||
AC300.11.10-004.20 | Pressure transducer 0-10bar 4-20mA with 4m cable | ||||||||
AC300.11.16-004.20 | Pressure transducer 0-16bar 4-20mA with 4m cable | ||||||||
AC300.11.25-004.20 | Pressure transducer 0-25bar 4-20mA with 4m cable | ||||||||
AC300.20.01-005.00 | Piezoresistive probe 4-20mA with 5m cable | ||||||||
AC300.20.01-010.00 | Piezoresistive probe 4-20mA with 10m cable | ||||||||
AC300.20.02-010.20 | Piezoresistive probe 4-20mA with 10m cable for sewage |
For more optionals click here
SPARE PARTS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
AC100.22/1/50 | Display electronic board with flat cable 20pin 50cm | ||||||||
AC100.22/1/80 | Display electronic board with flat cable 20pin 80cm | ||||||||
AC100.22/1/100 | Display electronic board with flat cable 20pin 100cm | ||||||||
SD687.20/1 | Three-phase MULTIPLUS 1 electronic board 20A | ||||||||
SD687.30-40/1 | Three-phase MULTIPLUS 1 electronic board 30-40A | ||||||||
SD687.60/1 | Three-phase MULTIPLUS 1 electronic board 60A | ||||||||
SD6987.100/1 | Three-phase MULTIPLUS 1 electronic board 100A | ||||||||
SD687.200/1 | Three-phase MULTIPLUS 1 electronic board 200A |